PV500-44 12/13INSTALLATION & MAINTENANCE MANUAL POWER VT PLUS WATER HEATER MODELS (40, 50, 75, 90, 100) LX 125 A-PVIF MODELS (50, 75, 90, 100)
Power VT® Plus WATER HEATER10 PV500-44 12/133.5 Service Clearances Allow sufficient space to provide adequate clearances on all sides for service a
Power VT® Plus WATER HEATER11 PV500-44 12/13 SINGLE STORAGE WATER HEATER WITH SUPPLEMENTAL STORAGE TANK TWO WATER HEATERS WITH REVERSE RETURN PIP
Power VT® Plus WATER HEATER12 PV500-44 12/135 CONDENSATE DRAIN, TRAP & DISPOSAL The POWER VT PLUS water heater is designed to produce signif
Power VT® Plus WATER HEATER13 PV500-44 12/135.1 Condensate Neutralization System (optional) Although only slightly acidic (3-5 PH), condensate ca
Power VT® Plus WATER HEATER14 PV500-44 12/136.3 Inlet Pressure Measure at the inlet pressure tap located at the main gas cock. The inlet pressure m
Power VT® Plus WATER HEATER15 PV500-44 12/13 6.6 Appliance Isolation during Gas Supply Piping Pressure Test 1. The appliance and its provided ma
Power VT® Plus WATER HEATER16 PV500-44 12/137 COMBUSTION AND VENTILATION AIR Provisions for adequate combustion and ventilation air to the mecha
Power VT® Plus WATER HEATER17 PV500-44 12/13 Duct Fitting Equivalent Length Duct Pipe: 6” Duct 7” Duct 8” Duct 9” Duct 90º Elbow 8 feet 9 fe
Power VT® Plus WATER HEATER18 PV500-44 12/138 VENTING 8.1 Venting the Power VT Plus “SANI” models: Power VT Plus models with “SANI” in the model n
Power VT® Plus WATER HEATER19 PV500-44 12/13The following vent information is provided for use in design calculations, if needed. Venting Specific
Power VT® Plus WATER HEATER2 PV500-44 12/13 TABLE OF CONTENTS 1. Safety Considerations 2. Product Descriptions 3. Water Heater Installation 3.1
Power VT® Plus WATER HEATER20 PV500-44 12/138.5 Vertical or Horizontal Vent Termination: 1. The vent terminal must have a minimum clearance of 4
Power VT® Plus WATER HEATER21 PV500-44 12/139 OPERATING AND SAFETY CONTROLS WARNING: Turn off all electrical service to the appliance when accessi
Power VT® Plus WATER HEATER22 PV500-44 12/1310 TEMPTRAC™ ELECTRONIC CONTROLLER PANEL 10.1 Principle Of Operation The water heater operates to s
Power VT® Plus WATER HEATER23 PV500-44 12/1310.5 To View The Setpoint Push and release the SET key to see the set point value. To return to
Power VT® Plus WATER HEATER24 PV500-44 12/1310.8 LED Display Alarm Messages Alarm messages are displayed in the upper LED readout and alternate wi
Power VT® Plus WATER HEATER25 PV500-44 12/1311.2 The Following Describes The Functions Of Each Of These Terminals And The Factory-Installed Option
Power VT® Plus WATER HEATER26 PV500-44 12/134. Proof of Air Pressure Switch - The control will look for a signal from the airflow-proving switch,
Power VT® Plus WATER HEATER27 PV500-44 12/1313 INITIAL STARTUP 13.1 Initial Startup Requirements Installation should be complete prior to perfor
Power VT® Plus WATER HEATER28 PV500-44 12/13b. Attach a manometer to measure the gas pressure at the manual gas shutoff valve located just upstrea
Power VT® Plus WATER HEATER29 PV500-44 12/1319. When the blower motor starts, the flame control will check for a positive air flow. If the air swi
Power VT® Plus WATER HEATER3 PV500-44 12/139. Operating and Safety Controls 9.1 Temperature and Pressure Relief Valve(s) 9.2 Operating Temper
Power VT® Plus WATER HEATER30 PV500-44 12/13 Gas Train Illustration for Models 40 through 50 (Optional components may not be shown) Gas
Power VT® Plus WATER HEATER31 PV500-44 12/1314 TROUBLESHOOTING GUIDE Problem Probable Cause Corrective Action Starting or Pre-purge Failure Po
Power VT® Plus WATER HEATER32 PV500-44 12/1315 REPLACEMENT PARTS REPLACEMENT PARTS
Power VT® Plus WATER HEATER33 PV500-44 12/1315.1 Control Panel
Power VT® Plus WATER HEATER34 PV500-44 12/1315.2 Control Panel Components (Optional components may not be included) Key No. Part No. Description
Power VT® Plus WATER HEATER35 PV500-44 12/1315.3 Burner Assembly Optional components may or may not be shown
Power VT® Plus WATER HEATER36 PV500-44 12/1315.4 Burner Assembly Components (Optional components may not be included) Item No. Qty. PVI Part No
Power VT® Plus WATER HEATER37 PV500-44 12/1316 PERIODIC MAINTENANCE Listed below are items that must be checked to ensure safe reliable operations.
Power VT® Plus WATER HEATER38 PV500-44 12/136. If equipped, the combustion air filter should be replaced every six months. If filter blockage beco
Power VT® Plus WATER HEATER39 PV500-44 12/1317 RECOMMENDED MAINTENANCE SCHEDULE 1. Annual Maintenance a. Check all joints and pipe connections fo
Power VT® Plus WATER HEATER4 PV500-44 12/131 SAFETY CONSIDERATIONS WARNING: If the information in the supplied manual(s) is not followed exactl
Power VT® Plus WATER HEATER40 PV500-44 12/13PVI INDUSTRIES®, LLC 3209 Galvez Ave. Fort Worth, Texas 76111 Phone 1-800-433-5654 www.pvi
Power VT® Plus WATER HEATER5 PV500-44 12/13 IMPORTANT SAFETY NOTE It takes only 5 seconds of skin contact with 140°F water to cause a second de
Power VT® Plus WATER HEATER6 PV500-44 12/132 PRODUCT DESCRIPTION Component, Controls and Connection Locations (Locations May Vary) 125 SERIES
Power VT® Plus WATER HEATER7 PV500-44 12/13250 SERIES
Power VT® Plus WATER HEATER8 PV500-44 12/13300 SERIES
Power VT® Plus WATER HEATER9 PV500-44 12/133 WATER HEATER INSTALLATION 3.1 Checking Equipment Before You Install Inspect the unit completely up